Properly maintained ladders are essential to the safe and economical operation of a fire department. Firefighters rely on the ladders to perform structurally and mechanically as intended.
WHEN SHOULD GROUND LADDERS BE TESTED?
NFPA 1932 contains the following requirements pertaining to frequency of ground ladder testing:
An annual inspection and test program uncovers many defects before they become major problems, thus resulting in better safety precautions and lower maintenance costs.
American Test Center will perform a thorough test and inspection at your site by a well-equipped two-person crew of non-destructive technicians who are experienced in structural testing. They are supported by a staff of engineers, ASNT NDT technicians and equipment specialists.
American Test Center performs the following tests and inspections:
I. STRUCTURAL
A. Visual Inspection: A complete visual inspection of:
B. Hardness Testing: Hardness testing is done on aluminum ladders as needed. Heat affected (annealed) areas on aluminum ladders are not visible to the naked eye, thus it is necessary to perform a hardness test, and a load test to determine its strength. The hardness service test is performed along the top and bottom of both beams.
C. Liquid Penetrant Testing: This test method is used on ground ladders made of aluminum material to verify discontinuities determined by visual inspection.
II. SERVICE TESTING
A. Horizontal Bending Test: (For all ladders except pompier ladders)
A load is applied to ladder in a horizontal position, with the ladder supported at the ends and loaded in the center. After successfully completing the loading process the ladder checked to ensure it retains it's original shape, criteria for this is established for each ladder type in NFPA 1932.
B. Ladder Hardware Test (Extension ladders only)
A specially designed test fixture is used to load the ladder across each extension lock assembly. The ladder locks must be in the set or locked position. The test load shall be applied for a minimum of one minute. Ladders shall sustain this test with no permanent deformation or other visible weakening of the structure.
C. Roof Ladder Hook Test (Ladders with roof hooks)
Apply the test load for a period of one minute to the roof hooks. The ladder and hooks shall sustain this test load with no permanent deformation or other visible weakening of the structure. Deformation to the hooks shall not exceed specifications. Note: Roof hooks should measure 3/4 inch diameter or 5/8 inch should be made of alloy steel.
III. REPORTS
Test defects are listed on American Test Center test report forms and described in detail on a comment sheet. Defects are classified for degree of severity. After the test, American Test Center personnel will review the report with the department representative. A signed, dated copy of the test report listing the defects discussed is left with the department. The reports are then subjected to a quality review by American Test Center's professional staff.
IV. SCHEDULING
American Test Center schedules tests with each fire department to best meet their individual requirements throughout the year. American Test Center has crews located throughout the United States to perform the tests at the fire department location. American Test Center encourages your department to have a representative present during the tests to observe and ask questions. American Test Center is flexible and will modify our standard testing procedures to meet your particular needs.
American Test Center
BOX 408, 2773 PRAIRIE DR, RIVER FALLS, WI 54022, US
Copyright © 2022 American Test Center - All Rights Reserved.